Multifunction meters – 2 channels of 3 phases
Basic data
The TNM160 is a universal multifunction measuring device with two channels of three phases each for DIN rail mounting. Up to six single-phase or two three-phase feeders can be measured via six current transformer inputs.
By using a TNM160 two-channel multifunction meter, the application of another multifunction meter can be saved.
It includes energy consumption recording and supports BACnet and Modbus protocols. The meter can be operated and configured via a web browser using the Ethernet TCP/IP interface.
An indispensable aid for displaying and evaluating via additional software the min/max values, active, apparent and reactive power, and harmonics up to 64en, as well as all important measured variables.
Auxiliary voltage |
90 – 250 VAC, 50/60 Hz
110 – 280 VDC
6 VA
|
Dimensions (WxHxD) |
160 x 97 x 65 mm |
Weight |
650 g |
Accuracy |
Active power 0.2%
Reactive power 0.2%
|
Environmental conditions |
Operation -20 – 70 °C
Storage -20 – 80 °C
Humidity 0 – 95 RH
|
Display |
85 x 64 Farbdisplay |
IP protection class |
IP64 |
Channels / Current inputs |
2 / 6 |
Sampling rate |
1600 |
Digital input/output |
2 / 1 |
Harmonic harmonics |
64 |
Harmonic distortion |
I-THD / U-THD |
Supported current transformers |
1A / 5A |
Current |
0.001 – 6 A |
0.10000 A – 999999 kA |
– overload (RMS constant) |
50 A |
|
– short term (for 1 minute) |
100 A |
|
– burden |
< 0.05 VA |
|
voltage L-L |
0 – 950 V |
0.10000 V – 999999 kV |
Voltage L-N |
0 – 550 V |
0.10000 V – 999999 kV |
– maximum (RMS constant) |
1000 V |
|
– Burden |
0.06 V |
|
Frequency |
45.001 – 65.001 Hz |
45.001 – 65.001 Hz |
Power factor (cap./ind.) |
-1 + 1 |
-1 + 1 |
Active power total/phase |
0.10000000 W – 999999999 MW |
|
Reactive power total/phase |
0.10000000 VAR – 999999999 MVAR |
|
Apparent power total/phase |
0.10000000 VA – 999999999 MVA |
|
Active power total/phase |
0.100000 WH – 9999999 MWH |
|
Reactive power total/phase |
0.100000 VARH – 9999999 MVARH |
|
Apparent work total/phase |
0.100000 VAH – 9999999 MVAH |
|
Total harmonic distortion V/I |
0.000 – 100.0 % |
|
Partial Harmonic Distortion V/I |
0.000 – 100.0 % |
Communication
BACnet |
MS/TP and TCP/IP |
Modbus |
RS485 and TCP/IP |
Browser-enabled |