WINDOW TYPE CURRENT TRANSFORMER

IBA

Dis. in mm: 63 x 56 x 29
Pri. bar: 20×5 mm; ⌀ 16
Range: 40… 200 A
Catalogue

IBP

Dis. in mm: 60 x 56 x 29
Pri. bar: 20 x 10 mm; ⌀ 18
Range: 100… 600A
Catalogue

IB

Dis. in mm: 105 x 76 x 38
Pri. bar: 30 x 10 mm; ⌀ 23
Range: 50… 600A
Catalogue

IB-50

Dis. in mm: 105 x 76 x 50
Pri. bar: 30 x 10 mm; ⌀ 23
Range: 100… 600A
Catalogue

IBG

Dis. in mm: 105 x 76 x 38
Pri. bar: 40 x 10 mm; ⌀ 30
Range: 150… 1000A
Catalogue

IBG/1

Dis. in mm: 105 x 76 x 38
Pri. bar: ⌀ 40
Range: 150… 1000A
Catalogue

IBR

Dis. in mm: 115 x 90 x 40
Pri. bar: 50×15/ 2x40x10; ⌀ 30
Range: 400… 1600A
Catalogue

IBR/1

Dis. in mm: 115 x 90 x 40
Pri. bar: 60×12/ 2x50x10; ⌀ 44
Range: 400… 1600A
Catalogue

IER

Dis. in mm: 155 x 133 x 46
Pri. bar: 80×10/ 2x60x10; ⌀ 50
Range: 250… 2000 A
Catalogue

IER-1

Dis. in mm: 155 x 133 x 46
Pri. bar: ⌀ 80
Range: 250… 2000 A
Catalogue

IER-2

Dis. in mm: 155 x 133 x 46
Pri. bar: 3 x 60 x 10 mm
Range: 250… 2000 A
Catalogue

IER-3

Dis. in mm: 155 x 133 x 46
Pri. bar: 2 x 80 x 10 mm
Range: 250… 2000 A
Catalogue

IER-4

Dis. in mm: 155 x 133 x 46
Pri. bar: 2 x 100 x 10 mm
Range: 250… 2000 A
Catalogue

IRP

Dis. in mm: 165 x 120 x 59
Pri. bar: 100 x 20 mm
Range: 750… 2500 A
Catalogue

IRM

Dis. in mm: 180 x 120 x 59
Pri. bar: 2 x 100 x 20 mm
Range: 1500… 4000 A
Catalogue

ICM

Dis. in mm: 182 x 140 x 60
Pri. bar: 3 x 100 x 10 mm
Range: 750… 3000 A
Catalogue

ICG

Dis. in mm: 228 x 190 x 103
Pri. bar: 3 x 130 x 20 mm
Range: 3000… 6000 A
Catalogue

IBO

Dis. in mm: 105 x 76 x 38
Range: Form A 5… 20A/
Form B 25… 150A
Catalogue
Conditions of use
Secondary current
5 A oder 1 A
Nominal frequency
50 – 60 Hz
max. permissible operating voltage
720 V
Test voltage
3 kV / 1 min
Thermal rated continuous current
Icth = 1,2 x Ipr
Thermal rated short-time withstand current
Ith = 60 x Ipr
Rated impulse current
Idyn = 2,5 x Ith
Overcurrent rating (FS)
n < 5
Insulation class
E / F / H
Normative standards
IEC 61869 Teil 1 + 2 / DIN EN 42600
Housing
Gehäuse aus selbstverlöschendem PA66 V0 nach UL 94
Environmental conditions
Installation location
Indoor use
Ambient temperature (operation)
-40°C … +60°C
Ambient temperature (storage / transport)
-40°C … +60°C
Altitude
up to 1000 m